HOME    Electricity    DIN Rail Split Type Prepaid Electricity Meter
DIN-split

DIN Rail Split Type Prepaid Electricity Meter

The CA168 Meter is a split type compact DIN Rail mounted Class 1 accuracy single phase electricity meter built in 35mm international standard housing made of poly-carbonate flame retardant materials. Galvanic isolation wire is basic connection between the meter and keypad. Double circuit measurement and relay are also available on request for reinforced tamper prevention

Main Features

  • 20 digit (Standard Transfer Specification) STS encryption
  • Slim-line and space-economy design,
  • Up to 13kV/6.5kA surge protection for lightening and other line surges
  • Up to 80A current with Class 1 accuracy
  • Disconnects on overload and no credit
  • Programmable power limit and low credit warning

 

Split Configuration for Increased Revenue Protection

The meter consists of two parts, the MCU (Metering & Control Unit) and UIU (User Interface Unit). The MCU and UIU is linked via galvanically-isolated 2-wire communication cable. Power line carrier (PLC) and Radio Frequency (RF) communication module is also available on request. The UIU is installed within consumer’s home, while MCU is installed in a meter cabinet away from consumers.

 

User benefit

Meter is durable and operable for harsh and severe environment 

Easy and quick to install 

Disconnect on preset credit level and tamper.

Slim-line design to reduce operational cost

Electrical parameters:

Voltage

Nominal voltage Un

230V

Limited voltage

70%~120%Un

Frequency

 

Nominal frequency fn

50-60Hz

tolerance

5%

Current

 

Basic current(Ib)

5A

Maximum current(Imax)

80A

Starting current(Ist)

20mA

Active energy constant

1600imp/kWh

Measurement Accuracy

 

Active energy to IEC62053‐21

Class1.0

Burden

 

Voltage circuit

<2W  <8VA

Current circuit

<1VA

Temperature range

 

Operation meter

-25℃ to+70℃

Storage

-40℃ to+85℃

 

Insulation

Insulation level

4kV rms 1min

Voltage impulse withstand

8kV 1.2/50 μs

Insulation System Classification

Protective Class II

Electro Magnetic Compatibility

Electrostatic discharges

 

Contact discharge

8kV

Air discharge

16kV

Electromagnetic RF fields

 

27MHz to 500MHz typical

10V/m

100kHz to 1GHz typical

30V/m

Fast transient burst test

4kV

Mechanical requirements

 

Meter shell Protection Rate

IP54

Insulation System Classification

Protective Class II

Maximum cable size

8 mm

 